EFP - ACI Floating Point to Pneumatic Transducer, 24VAC/DC/50/150mA Input, 0 - 10/0 - 15/0 - 20 psig Output

EFP - ACI Floating Point to Pneumatic Transducer, 24VAC/DC/50/150mA Input, 0 - 10/0 - 15/0 - 20 psig Output
$143.50

Availability: Non-Stock Item

ITEM USUALLY SHIPS IN 7-10 BUSINESS DAYS
EFP - ACI
DESCRIPTION

The EFP converts a floating point signal into a proportional pneumatic signal ranging from 0 - 20 psig. It is designed with electrical terminals on one end and pneumatic connections on the other, allowing for maximum convenience in wiring and tubing installation when panel mounted. The EFP is a constant bleed interface with branch exhaust response time determined by the bleed orifice and pressure differentials. If power fails to the EFP, it will continue to bleed through the bleed orifice until branch pressure is zero psig.

• Three way mixing valve control
• Pilot positioner control
• Compressor staging
• Fan vane control
• Rates of change - 45 sec, 90 sec, 1 min, 2 min (Standard), 30 sec, 3 min, 6 min, 8 min (Version 2)
• 24 VDC/AC at 1 A max override switch with N.O. in AUTO operation
• 1 Valve - 0.007" constant bleed orifice (41 scim)
• Floating point input source: Relay contact closure, Transistor or Triac

Product Information

Additional Information

Manufacturer ACI
Part Number EFP
Short Description EFP - Floating Point to Pneumatic Transducer, 24VAC/DC/50/150mA Input, 0 - 10/0 - 15/0 - 20 psig Output, 0.007" Orifice Valve with 41 scim Constant Bleed, 2%/3% Accuracy
Transducers Pneumatic Transducers
Voltage 24 VAC/DC
Input(s) Floating Point
Output(s) Pressure
Amperage Rating 50 mA, 150 mA Input on Pressure Excursions
Frequency 50/60 Hz
Range Input Signal Trigger Range: 9 - 24 VAC/DC Digital, Feedback Signal Range: 0 - 5 VDC = Output Span
Relative Humidity Range 5 to 95% Non-Condensing
Pressure Range Output Pressure Range: 0 - 10 psig (0 - 69 kPa), 0 - 15 psig (0 - 103 kPa) or 0 - 20 psig (0 - 138 kPa), Air Supply Pressure: 22 (151.69 kPa) - 28 (193.06 kPa) psig, Air Flow Pressure: 20 psig (138 kPa) Main, 15 psig (103 kPa) Out at Supply Valves
Product Series EFP Series
Accuracy 2% F.S.O. at Room Temperature/3% F.S.O. across 32 to 120
Standards/Approvals RoHS-Directive 2002/95/EC
Max Temperature 32 to 120
Warranty Information 2 Years Limited
Dimensions 4in x 3.35in x 1.87in